Electrical Power Supply: 24VAC, 3.6VA max, or 20 ~ 34VDC Consumption: 150mA max@24VDC Operating Temperature: 32° to 150° F (0° to 65° C) Storage Temperature: -4° to 150° F (-20° to 65° C) Operating Humidity: 10% to 95% relative humidity non-condensing
Communication
Physical Interface 1 (Port 1):
- EIA-485 (BUS A,B) Two-wire
- Half Duplex
- Baud Rate Speed: (9.6K, 19.2k, 38.4K, 76.8K bit/s)
- Data Bit: (8 bits)
- Application Protocol: BacnetMSTP Master
- Multi-drop Capability: Yes (hardware ID setting) Physical
Interface 2 (Port 2):
- Ethernet 10/100 Base-T
- Ethernet Support: IP,TCP,UDP,ICMP,IGMP,FTP,HTTP
- Application Support: BACnet IP, Bacnet Ethernet
Input/Output Configuration
Universal Input:
- 8 Channels
- Voltage: 0 - 10V (+/-0.005V) , 0 - 5V (+/- 0.003V)
- Current: 4 - 20mA (+/-0.01mA) , 0 - 20mA (+/-0.01mA)
- Resistance: 0 - 30K (+/-10 Ohm), 0 - 10K (+/-5 Ohm), 0 - 1.5K(+/-1 Ohm)
- Thermistor: 10K, 10K Shunt, 1K Balco, 1K Platinum : All (+/-0.01°C)
Digital Input:
- 8 Channels
- Type: Voltage Free
- Limit: +5V at 500Ohm Resistance maximum Digital Output:
- 8 Channels
- Type: Relay Contacts, SPST NO, 48VA at 24VAC, Pilot Duty
Transistor Output:
- 2 Channels
- Type: Open Collector Output, Isolation 3.75KV
- Max Rating: 1A, 60V Analogue Output
- 4 Channels (12 bits resolution)
- Type: Current: 0 - 20mA, 4 - 20mA (up to 800 Ohm load), Voltage: 0 - 10V
Mechanical:
- Dimension: 187mm x 110mm x 47mm
- Material: UL94 ABS
- Weight: 400g
|
Input/Output 1) Digital Input 2) Digital Output 3) PWMControl (Open Collector Output) 4) Analogue Input 5) Analogue Output 6) Digital & Analogue Internal Register 7) Multi-state 8) Fan Control 9) Digital State Latch 10) Digital State Timer 11) Digital State Counter 12)Digital Input Expander
Loop/Process 13) Thermostat 14) Loop Control (PID) 15) Drive 16) Selection 17) Flow Detect 18) Momentary Start/Stop 19) Totaliser 20) Pulse Accumulator 21) Analogue Limit 22) Set Point Adjust 23) Digital Alarm 24) Analogue Alarm
Conversion 25) Digital to Analogue 26) Analogue to Digital 27) Analogue to Percentage 28) Percentage to Analogue 29) Scaling 30) Table Conversion
Schedule 31) Holiday 32) Scheduler 33) Optimum Start/Stop
Timer/Sequencer 34) Sequencer 35) Timer Function
Others 36) Coil Output Register Binding 37) Holding Register Binding
|